SCANTRIC LOGO NETCONTROLS LW-E03
LW-E03 Picture NETCONTROLS LW-G03
3 Phase Energy Meter Module

The LW-G03 is intended to work in LonWorks FT-10 networks and perform 3 phase energy and power measurement. It has 3 voltage and 3 current AC inputs.
The module accepts voltages in the range 0 - 500 Vac, and currents from 0 to 5 Aac. External current and voltage transformers are required to meter signals out of these ranges.
The analog digital converter has a 16 bit resolution and the overall accuracy is 0.2 %.
Block Diagram Applications
  • Electric, Gas and Water Utilities
  • Factory Automation
  • Intelligent Buildings
Among many others.




Terminal Description
No. Function No. Function
13 Power Supply +V 25 Ph. S Current Input Negative (I-)
14 Power Supply GND 26 Ph. S Current Input Positive (I+)
15 FT-10 Network 27 Ph. S Voltage Input Negative (V-)
16 FT-10 Network 28 Ph. S Voltage Input Positive (V+)
    29 Ph. T Current Input Negative (I-)
19 Ph. R Current Input Negative (I-) 30 Ph. T Current Input Positive (I+)
20 Ph. R Current Input Positive (I+) 31 Ph. T Voltage Input Negative (V-)
21 Ph. R Voltage Input Negative (V-) 32 Ph. T Voltage Input Positive (V+-)
22 Ph. R Voltage Input Positive (V+)    
Technical Specifications
Power Supply 8 - 24 Vdc
Consumption < 80 mA
Number of Input Channels 3 for AC Voltage
3 for AC Current
Voltage Input Range 0 - 500 VAC (peak)
Current Input Range 0 - 5 AAC (peak)
Overall analog accuracy 0.2% of full scale
Analog-digital conversion precision 16 bit
Communication Channel LonWorks FT-10 (78 kbps)
Operation Temperature -10º C to 55º C
Dimensions L x W x H: 105 x 90 x 70 mm
Mounting DIN rail
Visual Indications Two 3 mm leds (Power and Status)


www.atechna.com